Submit RFQ
LAMTEC LT1 image 1

LAMTEC LT1 Oxygen Measuring System for LS1 Lambda Probe

LAMTEC

Model / Part Number: LT1

Availability subject to quotation and stock confirmation

Supplied for maintenance, retrofit and replacement projects. Exact suffix, configuration and condition must be confirmed before ordering.

pcsRequest a Quote
WhatsApp InquiryResponse within 1 business day
BrandLAMTEC
Model / Part NumberLT1
Country of OriginConfirm by lot

Independent supplier; model, suffix, condition and availability require confirmation.

▣ Product Overview

LAMTEC LT1 is a modular oxygen transmitter system designed to work with the LS1 zirconia oxygen probe. It is used for continuous measurement of oxygen concentration in flue gases from boilers, furnaces, and industrial combustion processes. The LT1 is a configurable product, and before quotation it is necessary to confirm the housing type, power supply, display, flue gas pump, calibration unit, signal outputs, communication interfaces, as well as the LS1 probe and installation accessories.

LAMTEC LT1 is a modular, microprocessor-based oxygen measuring system designed for use with one LAMTEC LS1 lambda probe. It continuously measures oxygen concentrations from 0 to 21 vol.% in combustion flue gases, furnace atmospheres and suitable process gases in the superstoichiometric range (λ > 1).

The system provides automatic calibration with ambient air at 20.96 vol.% O₂, automatic ageing compensation of the ZrO₂ measuring cell and an accuracy of ±0.1 vol.% O₂ after calibration. Depending on the selected configuration, LT1 can provide analogue and digital inputs and outputs, LAMTEC SYSTEM BUS, PROFIBUS DP, Modbus RTU and additional combustion-optimisation functions.

LT1 is available in wall-mounting, mounting-plate and 19-inch panel-installation versions. The complete order code, power supply, enclosure, display, pump, calibration unit, outputs, communication interface, LS1 probe and installation accessories must be confirmed before quotation.

Datasheets

⚙ Technical Specifications

Oxygen measuring range0–21 vol.% O₂
Measurement accuracy after calibration±0.1 vol.% O₂
Measurement resolution0.01 vol.% O₂
Compatible lambda probeLS1; one probe per LT1
Automatic calibration referenceAmbient air, 20.96 vol.% O₂
Analogue outputs1 standard; up to 4, configuration dependent 0/4–20 mA or 0–10 V
Digital outputs1 standard plus 6 optional outputs
Power supply115 or 230, configuration dependent VAC
Communication interfacesLAMTEC SYSTEM BUS; optional PROFIBUS DP, Modbus RTU and RS 422

▰ Availability & Delivery

Availability & DeliveryAvailability subject to quotation and stock confirmation
Lead TimeRFQ confirmation required
Shipping OptionsAir freight, sea freight, express
PackagingSecure export packaging